Index | Identifier | Required | Example |
---|
12 | application-software-version | Yes | string |
24 | daylight-savings-status | No | data |
28 | description | No | data |
44 | firmware-revision | Yes | string |
56 | local-date | No | data |
57 | local-time | No | data |
58 | location | No | data |
70 | Model_Name | Yes | 'CPO-PC-6A' |
75 | Object_Identifier | Yes | Device Number |
76 | object-list | Yes | Analog Input #1, Analog Input #2, ... |
77 | object-name | data | 'AHU201' |
96 | protocol-object-types-supported | Yes | data |
97 | protocol-services-supported | Yes | readProperty, writeProperty, .. |
98 | protocol-version | Yes | data |
112 | System_Status | Yes | Enumerated data |
121 | vendor-name | Yes | 'Honeywell' |
139 | protocol-revision | data | data |
154 | configuration-files | data | data |
157 | last-restore-time | data | data |
tablerow | data | data | data |
PROPERTY BACnet EXAMPLE
Object_Type Required Device
Vendor_Identifier Required Alerton
Protocol_Conformance_Class Required 2
Protocol_Object_Types_Supported Required Analog Input, Analog Output,...
Max_APDU_Length_Supported Required 50 (bytes or characters)
Segmentation_Supported Required No
VT_Classes_Supported Optional n/a
Active_VT_Sessions Optional n/a
Local_Time Optional 12:30:15.22
Local_Date Optional Tuesday, March 12, 1996
UTC_Offset Optional +480 (minutes from GMT/UTM)
Daylight_Savings_Status Optional False (not in effect)
APDU_Segment_Timeout Optional n/a
APDU_Timeout Required 3000 milliseconds
Number_Of_APDU_Retries Required 0
List_Of_Session_Keys Optional n/a
Time_Synchronization_Recipients Optional n/a
Max_Master Optional n/a
Max_Info_Frames Optional n/a
Device_Address_Binding Required None