up: embedded systems - modbus  
Modbus
Message Format
What links here?
Modbus RTU
Field size range of values
slave address 8 bits 0-255 (1)
function code 8 bits commands
data variable0 to 252 bytes
Error check 16 bitsCRC


Request
ByteMeaning
1Slave Address
2Function Code
3Address of first register (high)
4Address of first register (low)
5Total number of registers requested (high)
6Total number of registers requested (low)
7CRC (low)
7CRC (high)


Response
ByteMeaning
1Slave Address
2Function Code
3Number of bytes following (not including CRC)
4Byte 1
5Byte 2
3 + n + 1CRC (high)
3 + n + 2CRC (low)